ocan_od: Architecture and Design Description

1. Block diagram

Block diagram of ocan_od: access decoder and rule check (OD-1), protected parameters with the compare and the
repair (OD-2), outputs to the blocks and the error register (OD-3), application port (OD-4)

ocan_od is one entity with a two-process design. An access of ocan_sdo is decoded and checked in one clock cycle and answered in the next; an access to an object of the user logic passes the application port. Every writable parameter is held in two copies; the outputs to the blocks are derived from the copies in every cycle.

2. Access path (OD-1)

2.1 Access interface

ocan_sdo presents an access with Acc_Valid; Acc_Ready is '1' while no access of the application port is outstanding. The data bytes are a value: byte k of the transfer (byte 0 first on the bus) is in bits 8k + 7 to 8k of Acc_Data and Rsp_Data, so that an UNSIGNED32 written as 78h, 56h, 34h, 12h is the value 12345678h.

Signal Content
Acc_Write '1' write, '0' read
Acc_Index, Acc_Sub Index (16 bits) and sub-index (8 bits)
Acc_Data, Acc_Len Data bytes of a write (64 bits) and their number (1 to 8; 0 not indicated: the size of the data type is taken)
Rsp_Valid One-cycle answer
Rsp_Data, Rsp_Len Data bytes of a read and their number
Rsp_Abort Abort code; 0 for a successful access

2.2 Decoder

A combinational function maps index and sub-index to an object of table 1 of the specification, with its data type, access type and the NMT states in which a write is allowed, for the generics. Indices from 2003h to 9FFFh go to the application port. An index of table 1 is decoded only when its object exists for NumRpdo_g, NumTpdo_g and TimePdos_g.

2.3 Rule check and the order of the abort codes

The checks of a write run in this order; the first failing check gives the abort code:

Order Check Abort code
1 Object exists 0602 0000h
2 Sub-index exists 0609 0011h
3 Access type (write of ro or const, read of wo) 0601 0002h, 0601 0001h
4 Number of data bytes, when indicated (Acc_Len 1 to 8) 0607 0012h, 0607 0013h
5 NMT state (OD-WR-03) 0800 0022h
6 Value: unsupported COB-ID bits, change while valid, restricted or free identifier, transmission type, 1016h, Bdefault 0609 0030h
7 Duplicate identifier 0604 0043h

Checks 6 and 7 compare the written COB-ID with the stored one and with the effective identifiers of the other entries (section 3.1). The restricted identifiers are those of [CiA301] section 7.3.5, table 40, and the free ranges of clause 9.5a, as constants of the entity. A read runs checks 1 to 3.

2.4 Answer

The answer of an access to an own object is registered: Rsp_Valid, data and abort code in the clock cycle after Acc_Valid and Acc_Ready. An accepted write updates both copies at the same clock edge (OD-WR-09). A reset application or reset communication event in the cycle of an access sets the objects to their power-on values; the write has no effect, and the access is answered with the abort code 0800 0022h, which ocan_sdo does not send because the reset ends its transfer.

3. Protected parameters (OD-2)

3.1 COB-IDs

Each of the entries 0 to 10 of the COB-ID table is held in two copies CobA(e) and CobB(e) of 13 bits:

Field Bits Meaning
NotValid 1 Bit 31 of the COB-ID
Rel 1 '1': the identifier is the base of the pre-defined connection set plus the NODE-ID
Id 11 Identifier when Rel is '0'

The effective identifier of an entry is base(e) + Nmt_NodeId while Rel is '1' and Id otherwise; base(e) is 200h, 300h, 400h, 500h for the receive PDOs and 180h, 280h, 380h, 480h for the transmit PDOs. A reset communication sets Rel of these entries, so the identifiers follow the NODE-ID of the new sample (OD-RS-03); an accepted write stores the written identifier with Rel = '0'. The time PDOs and SYNC have Rel = '0' with the power-on values of the generics and 080h. Cfg_CobId is built from CobA, Cfg_CobIdCopy from CobB, with the same Nmt_NodeId: the valid flag of entry e is not NotValid. Entry 0 (SYNC) is always valid, since bit 31 of 1005h has no meaning for a consumer; entry 11 (master heartbeat) is 700h + the NODE-ID of 1016h sub-index 01h of the same copy, valid while that NODE-ID is not 0.

No repair: copies that disagree stay until a write or a reset communication (OD-PR-02). A read returns CobA: bit 31 is NotValid, bit 30 is '1' for a transmit PDO (no remote frames) and '0' for a receive PDO, whose reserved bit 30 is not stored at a write, bits 29 to 11 are 0 and bits 10 to 0 are the effective identifier. For 1005h bit 31 is stored as written and read back. Rel has an effect for the entries 2 to 9 only.

3.2 Other parameters

Parameter Width per copy Power-on value
1016h sub-index 01h: NODE-ID, time 7 + 16 MasterNodeId_g, MasterHbTime_g
1017h 16 ProducerHbTime_g
Transmission types of the receive and transmit PDOs 1 to 4 and of the time PDOs 8 each RpdoType_g, TpdoType_g, SctType_g, LtpType_g
Bdefault 1 Bdefault_g
Ttoggle, Ntoggle 8 each Ttoggle_g, Ntoggle_g

For each parameter Ok is the combinational equality of its copies. The output to the blocks and the value of a read is copy A while Ok is '1' and the power-on value otherwise (OD-PR-03). While Ok is '0' the next value of both copies is the power-on value, Err_ParamCopy pulses in that cycle and the latch ErLatch (bit 7 of 1001h) is set. An accepted write of the parameter in the same cycle takes precedence over the repair; the event and the latch are set all the same.

3.3 Test input

ErrInj_BitFlip has one bit per protected register bit of both copies; in a cycle with ErrInj_Valid = '1' the selected bits are inverted in the registers, after every other assignment of that cycle. The layout, from bit 0:

Bits Copy A Bits Copy B
0 to 142 CobA(0) to CobA(10), 13 bits each (Id in bits 10 to 0, Rel bit 11, NotValid bit 12) 279 to 421 CobB(0) to CobB(10)
143 to 165 1016h sub-index 01h (time in bits 15 to 0, NODE-ID in bits 22 to 16) 422 to 444 as copy A
166 to 181 1017h 445 to 460 as copy A
182 to 261 Transmission types: receive PDOs 1 to 4, transmit PDOs 1 to 4, Spacecraft Time PDO, Local Time PDO 461 to 540 as copy A
262 Bdefault 541 as copy A
263 to 278 Ttoggle (bits 263 to 270), Ntoggle (bits 271 to 278) 542 to 557 as copy A

The layout is the same for every value of the generics; bits of absent objects have no effect: the entries of absent objects in the COB-ID table are constant 0 in both copies, and the copies of the transmission types of absent PDOs are not compared, so that a flip there raises neither Err_ParamCopy nor, in ocan_dispatch, Err_CobId.

4. Outputs and updates (OD-3)

Output Source
Cfg_CobId, Cfg_CobIdCopy Section 3.1
Cfg_HbTime to ocan_nmt 1017h
Cfg_MasterHbTime, Cfg_Bdefault, Cfg_Ttoggle, Cfg_Ntoggle to ocan_redundancy 1016h sub-index 01h bits 15 to 0, 2000h sub-indices 01h to 03h
Cfg_Ctoggle, Cfg_CtoggleValid to ocan_redundancy Value and one-cycle event of an accepted write of 2000h sub-index 04h
Cfg_SctType, Cfg_LtpType, Cfg_SetValid, Cfg_SetScet to ocan_time 1404h and 1804h sub-index 02h; value and one-cycle event of an accepted write of 2001h
Cfg_RpdoType, Cfg_TpdoType to ocan_pdo Sub-index 02h of 1400h to 1403h and 1800h to 1803h
Stat_ErrReg 1001h

The update of Bdefault by ocan_redundancy (Upd_Valid, Upd_Bdefault) writes both copies, unless an accepted write of 2000h sub-index 01h comes in the same cycle (OD-WR-10). The local time (Stat_Scet) and Ctoggle (Stat_Ctoggle) of the blocks are read in the cycle of the access.

Error register. Bit 4 is '1' while Link_State (the fault confinement state of the controller of the active bus, as at olo_intf_can) is error passive or bus off; ocan_core selects the controller. Bit 7 is ErLatch. Bit 0 is bit 4 or bit 7 or a COB-ID entry whose copies disagree.

5. Application port (OD-4)

State App_ReqValid Exit
AppIdle_s '0' Access to an index from 2003h to 9FFFh: request registered, to AppReq_s
AppReq_s '1' App_ReqReady = '1': to AppWait_s
AppWait_s '0' App_RspValid = '1': answer with App_RspData, App_RspLen, App_RspAbort, to AppIdle_s

Acc_Ready is '0' outside AppIdle_s (OD-AP-02). App_RspValid is taken only in AppWait_s; a response in another state is ignored. TmoCnt counts the ticks in AppReq_s and AppWait_s; at a tick with TmoCnt >= 255 the access ends with 0800 0000h and the event Err_AppTimeout, and the port returns to AppIdle_s: a request that the user logic has not taken is withdrawn, a late response is ignored (OD-AP-03). The when others branch leads to AppIdle_s.

The default values of the inputs are App_ReqReady = '1', App_RspValid = '1', App_RspAbort = 0602 0000h: a port left unconnected answers every request with 0602 0000h two cycles after the request (OD-AP-04).

6. Resets

Event Effect
Rst Every register to its power-on value, Rel set, ErLatch cleared, the port in AppIdle_s
Reset application (Nmt_ResetApp) As reset communication; 2000h sub-indices 01h to 03h kept (OD-RS-02)
Reset communication (Nmt_ResetComm) Every parameter of 1000h to 1FFFh to its power-on value, Rel set, ErLatch cleared; an outstanding request of the application port ends without an answer

7. Minimal set

With MinimalSet_g = true, Acc_Ready is '0' and App_ReqValid is '0'. The parameters are constants of the generics, except Bdefault, which keeps its two copies and the update of OD-IF-04. The COB-IDs of the receive and transmit PDOs 1 to 4 have Rel = '1' and are valid; the transmission types are 254 (OD-MS-02). An assertion refuses TimePdos_g = true with NumRpdo_g or NumTpdo_g above 3 (OD-MS-05).

8. Ports of ocan_od

Signal Direction Width Default Description
Clk, Rst In 1 - Clock and synchronous high-active reset
Tick_Ms In 1 - Tick every millisecond
Acc_Valid, Acc_Ready, Acc_Write, Acc_Index, Acc_Sub, Acc_Data, Acc_Len In, Out, In, In, In, In, In 1, 1, 1, 16, 8, 64, 4 '0' for Acc_Valid Access of ocan_sdo
Rsp_Valid, Rsp_Data, Rsp_Len, Rsp_Abort Out 1, 64, 4, 32 - Answer
Nmt_State, Nmt_NodeId, Nmt_ResetApp, Nmt_ResetComm In 2, 7, 1, 1 - From ocan_nmt
Cfg_CobId, Cfg_CobIdCopy Out 144 - COB-ID table of ocan_dispatch
Cfg_HbTime Out 16 - Producer heartbeat time
Cfg_MasterHbTime, Cfg_Bdefault, Cfg_Ttoggle, Cfg_Ntoggle Out 16, 1, 8, 8 - To ocan_redundancy
Cfg_Ctoggle, Cfg_CtoggleValid, Stat_Ctoggle, Upd_Valid, Upd_Bdefault Out, Out, In, In, In 8, 1, 8, 1, 1 - Ctoggle and the update of Bdefault
Cfg_SctType, Cfg_LtpType, Cfg_SetValid, Cfg_SetScet, Stat_Scet Out, Out, Out, Out, In 8, 8, 1, 56, 56 "0" for Stat_Scet To and from ocan_time
Cfg_RpdoType, Cfg_TpdoType Out 32, 32 - Transmission types of the PDOs 1 to 4, 8 bits each
Link_State In 2 "00" Fault confinement state of the controller of the active bus
App_ReqValid, App_ReqReady, App_ReqWrite, App_ReqIndex, App_ReqSub, App_ReqData, App_ReqLen Out, In, Out, Out, Out, Out, Out 1, 1, 1, 16, 8, 64, 4 '1' for App_ReqReady Request of the application port
App_RspValid, App_RspData, App_RspLen, App_RspAbort In 1, 64, 4, 32 '1', 0, 0, 0602 0000h Response of the user logic
Stat_ErrReg Out 8 - Error register (1001h)
Err_ParamCopy, Err_AppTimeout Out 1 - Events
ErrInj_BitFlip, ErrInj_Valid In 558, 1 0, '0' Test inputs (section 3.3). A system ties them to 0

9. Configuration parameters

The generics of section 4 of the specification; the 32-bit values (DeviceType_g, VendorId_g, ProductCode_g, Revision_g, SerialNumber_g) are std_logic_vector(31 downto 0), the others natural with the ranges of the specification. Assertions refuse at elaboration: SctCobId_g or LtpCobId_g that is not 0 and restricted or free, two equal non-zero identifiers among them, NumRpdo_g or NumTpdo_g above 3 with MinimalSet_g and TimePdos_g, SctCobId_g or LtpCobId_g of 0 with MinimalSet_g and TimePdos_g (OD-MS-03), and a transmission type (RpdoType_g, TpdoType_g, SctType_g, LtpType_g) from 241 to 253, which the declared range 0 to 255 does not exclude (typeOk, the rule of OD-WR-06).

10. Timing and behaviour

Operation Duration
Access to an object of table 1 to Rsp_Valid 1 clock cycle
Accepted write to the new value at the outputs 1 clock cycle
Access to an object of the user logic to App_ReqValid 1 clock cycle
App_RspValid in AppWait_s to Rsp_Valid 1 clock cycle
Unconnected application port: access to Rsp_Valid (0602 0000h) 3 clock cycles
No response of the user logic 256 ticks to Rsp_Valid (0800 0000h) and Err_AppTimeout
Copies that disagree to the power-on value at the outputs 0 clock cycles (combinational); repaired copies in the next cycle
Reset communication to the power-on values 1 clock cycle