ocan_redundancy: Architecture and Design Description¶
1. Block diagram¶
ocan_redundancy is one entity with one two-process record. It instantiates no other entity and runs in Clk. The
encoding of Nmt_State is the NMT state encoding of ocan_pkg ("00" Initialisation, "01" Pre-operational, "10"
Operational, "11" Stopped; architecture of ocan_nmt, section 3).
2. Master heartbeat consumer (RM-1)¶
2.1 Heartbeat check¶
A master heartbeat on bus b is Rx_HbValid(b) with DLC 1 (RM-HB-01). An event with another DLC is ignored and gives
Err_HbDlc; events of both buses in one cycle give one pulse. The state byte is not checked. Stat_HbState holds
the state byte of the last master heartbeat on the active bus. An NMT message on bus b is Rx_NmtValid(b); the
dispatch has checked its DLC and addressing (DS-RX-03).
2.2 Presence per bus¶
Per bus a counter PresMs(b) (16 bits) and a flag Present(b) (Stat_HbPresent(b), RM-HB-05):
| Condition | PresMs(b) |
Present(b) |
|---|---|---|
Cfg_HbTime = 0 |
0 | '0' |
| Master heartbeat on bus b | 0 | '1' |
Tick_Ms, Present(b) = '1' and PresMs(b) >= Cfg_HbTime - 1 |
0 | '0' |
Tick_Ms and Present(b) = '1' |
PresMs(b) + 1 |
'1' |
The compare with >= also clears the presence at the next tick when Cfg_HbTime is lowered below the running count.
2.3 Timer¶
One timer serves the master heartbeat monitoring in Monitor_s and the toggling in Select_s and Switch_s. It
counts Ttoggle consumer heartbeat times with two counters, so that no multiplier is needed. T is Cfg_Ttoggle, read
as 1 when it is 0 (RM-HB-04); C is Cfg_HbTime.
| Register | Width | Function |
|---|---|---|
TmrMs |
16 | Ticks within the current consumer heartbeat time, 0 to C - 1 |
TmrPer |
8 | Consumer heartbeat times elapsed, 0 to T - 1 |
HbTimeReg, TtoggleReg |
16, 8 | Cfg_HbTime and Cfg_Ttoggle of the previous cycle |
At Tick_Ms with C /= 0, while the state is Monitor_s, Select_s or Switch_s: when TmrMs >= C - 1, TmrMs
:= 0 and TmrPer is incremented; when TmrPer is T - 1 at that point, TmrPer := 0 and the timer expires.
The timer expires every T x C ticks. With C = 0 it never expires (RM-HB-03). The compares with >= end a count above
its limit after an upset at the next tick.
A restart clears both counters. It happens at every master heartbeat on the active bus in Monitor_s, at the
start and at the end of a bus selection process, at a toggle, and when Cfg_HbTime /= HbTimeReg or
Cfg_Ttoggle /= TtoggleReg (RM-HB-04). A restart and a tick in the same cycle restart the timer; the tick is not
counted. The first expiry after a restart therefore lies between T x C - 1 and T x C milliseconds after it.
3. Bus selection process (RM-2)¶
| Register | Width | Content |
|---|---|---|
Fsm |
- | Idle_s, Monitor_s, Select_s, Switch_s |
ReqBus |
1 | Requested active bus (Link_Bus) |
Ctoggle |
8 | Toggles of the current process (Stat_Ctoggle) |
ToggleDue |
1 | A toggle has fallen due and waits for Pre-operational |
Exhausted |
1 | The end of the toggling was reported (Err_ToggleEnd), no further event until the next toggle |
EndAfter |
1 | The running switch ends the process (RM-SL-06) |
Stat_Selecting is '1' in Select_s and Switch_s. Stat_ActiveBus is Link_ActiveBus (RM-IF-04). The link
has ended a switch when Link_Switching = '0' and Link_ActiveBus = ReqBus.
A message on bus b is a master heartbeat (section 2.1) or an NMT message on bus b. The active bus is
Link_ActiveBus; the other bus is the inactive one.
| State | Condition (first match) | Action | Next state |
|---|---|---|---|
Idle_s |
MinimalSet_g = false and Nmt_State = Pre-operational |
Start-up process on Bdefault, no switch (RM-SL-01): Ctoggle := 0, ToggleDue, Exhausted and EndAfter := '0', restart |
Select_s |
Idle_s |
MinimalSet_g = true and Nmt_State /= Initialisation |
Monitoring starts (RM-MS-02): restart | Monitor_s |
Idle_s |
MinimalSet_g = false and Nmt_State Operational or Stopped (only after an upset of ocan_nmt) |
Monitoring starts (RM-SL-01): restart | Monitor_s |
Idle_s |
otherwise | ReqBus := Cfg_Bdefault |
Idle_s |
Monitor_s |
Timer expired | Err_HbMissing, Nmt_PreopReq (RM-HB-02, RM-SL-02); Ctoggle := 0, ToggleDue := '1', Exhausted and EndAfter := '0', restart |
Select_s |
Select_s |
Message on the active bus | End of the process (RM-SL-05): Upd_Valid with Upd_Bdefault = Link_ActiveBus, restart |
Monitor_s |
Select_s |
Message on the inactive bus only | ReqBus := the inactive bus, EndAfter := '1' (RM-SL-06); Ctoggle unchanged |
Switch_s |
Select_s |
ToggleDue = '1', Nmt_State = Pre-operational, C /= 0 and Ctoggle < Cfg_Ntoggle |
Toggle (RM-SL-03, RM-HB-03): ReqBus := not ReqBus, Ctoggle + 1, ToggleDue := '0', Exhausted := '0', restart |
Switch_s |
Select_s |
ToggleDue = '1' and Ctoggle >= Cfg_Ntoggle |
ToggleDue := '0'; Err_ToggleEnd when Exhausted = '0', then Exhausted := '1' (RM-SL-04) |
Select_s |
Select_s |
Timer expired | ToggleDue := '1' |
Select_s |
Switch_s |
The link has ended the switch, EndAfter = '1' |
Nmt_Switched; end of the process: Upd_Valid with Upd_Bdefault = ReqBus, EndAfter := '0', restart |
Monitor_s |
Switch_s |
The link has ended the switch | Nmt_Switched (RM-SL-03) |
Select_s |
Switch_s |
Master heartbeat or NMT message on the bus ReqBus |
EndAfter := '1' |
Switch_s |
Switch_s |
Timer expired | ToggleDue := '1' |
Switch_s |
In addition, an expiry in Select_s that leaves a toggle due while Nmt_State is Operational or Stopped gives
Nmt_PreopReq again (RM-SL-03): a request that ocan_nmt did not follow, or a return to Operational during the
process (an NMT message of the old bus delivered during a switch, a reset communication in the minimal set, an
upset of ocan_nmt), does not stop the toggling.
The when others branch leads to Monitor_s with a restart: the node keeps its bus, and a missing master heartbeat
starts a new bus selection. As in every core of the family, this recovery from an illegal state works only when the
synthesis tool implements the state machine safely: ocan_redundancy protects none of its registers itself, they
rely on the TMR and the safe state machines of the synthesis tool (protection scope of the user guide). Without an
upset of the state machine, every register recovers by itself: TmrMs and PresMs by the compares with >=, a
toggle that waits outside Pre-operational by the repeated request, Idle_s in Operational or Stopped by the start
of the monitoring, EndAfter at the start of every process.
- Same-cycle messages. A message on the active bus wins over one on the inactive bus in the same cycle (RM-SL-06, DS-BG-04).
- Outside the bus selection process messages of the inactive bus change nothing but the presence status
(RM-SL-07). In
Monitor_sa master heartbeat on the active bus restarts the timer; NMT messages do not. - Writes (RM-SL-09, RM-SL-10).
Cfg_Bdefaultis read inIdle_sonly.Cfg_CtoggleWrloadsCfg_CtoggleintoCtogglein any state, without a restart; a write in the same cycle as a toggle wins.Cfg_Ntoggleis compared at every toggle that falls due. The toggle invertsReqBus, so after an even number of toggles the node is on the bus on which the process started. - NMT resets do not reach
ocan_redundancy(RM-SL-08). After a reset communicationocan_nmtpasses the Initialisation again: a toggle that falls due meanwhile waits inToggleDue(RM-SL-03).
4. Ports of ocan_redundancy¶
| Signal | Direction | Width | Description |
|---|---|---|---|
Clk, Rst |
In | 1 | Clock and synchronous high-active reset |
Tick_Ms |
In | 1 | Pulse every millisecond (olo_base_strobe_gen of ocan_core) |
Rx_NmtValid |
In | 2 | Per bus: NMT message (RxRed_NmtValid of ocan_dispatch) |
Rx_HbValid, Rx_HbDlc, Rx_HbState |
In | 2, 8, 16 | Per bus: master heartbeat, its DLC and state byte (RxRed_Hb* of ocan_dispatch) |
Cfg_HbTime |
In | 16 | Consumer heartbeat time of the master in milliseconds (1016h sub-index 1, bits 15 to 0) |
Cfg_Bdefault |
In | 1 | Bdefault (2000h sub-index 1): '0' bus A, '1' bus B |
Cfg_Ttoggle, Cfg_Ntoggle |
In | 8, 8 | Ttoggle and Ntoggle (2000h sub-indices 2 and 3) |
Cfg_CtoggleWr, Cfg_Ctoggle |
In | 1, 8 | Write of Ctoggle (2000h sub-index 4): pulse and value |
Upd_Valid, Upd_Bdefault |
Out | 1, 1 | Update of Bdefault at the end of a bus selection process (clause 8.3.3l), to ocan_od |
Link_Bus |
Out | 1 | Requested active bus (Ctrl_Bus of ocan_link) |
Link_ActiveBus, Link_Switching |
In | 1 | Stat_ActiveBus and Stat_Switching of ocan_link |
Nmt_State |
In | 2 | NMT state (Stat_State of ocan_nmt, encoding of ocan_pkg) |
Nmt_PreopReq, Nmt_Switched |
Out | 1 | Pulses to ocan_nmt (Red_PreopReq, Red_Switched) |
Stat_ActiveBus |
Out | 1 | Active bus reported by the link (Red_ActiveBus of ocan_dispatch) |
Stat_Selecting |
Out | 1 | '1' during the bus selection process (Red_Selecting of ocan_dispatch and ocan_nmt) |
Stat_Ctoggle |
Out | 8 | Ctoggle, for reads of 2000h sub-index 4 |
Stat_HbState |
Out | 8 | State byte of the last master heartbeat on the active bus |
Stat_HbPresent |
Out | 2 | Per bus: a master heartbeat arrived within the last consumer heartbeat time |
Err_HbMissing |
Out | 1 | Event: master heartbeat missing for Ttoggle consumer heartbeat times |
Err_ToggleEnd |
Out | 1 | Event: Ntoggle toggles made without an active bus |
Err_HbDlc |
Out | 1 | Event: master heartbeat with a DLC other than 1 |
5. Configuration parameters¶
| Generic | Default | Range | Description |
|---|---|---|---|
MinimalSet_g |
false | true, false | Minimal protocol set of clause 9: no start-up bus selection (Idle_s to Monitor_s) |
6. Timing and behaviour¶
| Operation | Duration |
|---|---|
Rx_* event to the action of section 3 (Upd_Valid, Link_Bus, Stat_Selecting) |
1 clock cycle |
Timer expiry in Monitor_s to Err_HbMissing and Nmt_PreopReq |
1 clock cycle after the tick |
Nmt_State = Pre-operational to Link_Bus of the first toggle |
1 clock cycle |
End of the switch at the link to Nmt_Switched |
1 clock cycle |
| Missing master heartbeat | Between T x C - 1 and T x C ms after the last master heartbeat on the active bus |
| Toggle period | T x C ms from a toggle to the next due toggle, the switch time of the link included |
Every event of ocan_dispatch is processed in the cycle after it, also events of both buses in one cycle and in
consecutive cycles (RM-IF-08).